THE INTEGRATION OF PUMPED STORAGE STATIONS IN THE BRAZILIAN NATIONAL INTEGRATED SYSTEM: ELECTRICAL SYSTEM BEHAVIOUR ANALYSIS

Autores

  • Jiri Koutnik Voith
  • Maria R. G. Zoby Voith
  • Manuel N. F. Gonçalves Voith
  • Rafael A. Lopes Voith

DOI:

https://doi.org/10.26512/ripe.v2i4.21460

Palavras-chave:

Pumped storage. Stability. Numerical modelling.

Resumo

The increasing share of renewable sources of energy introduces new issues in terms of system operation and equipment design. The insertion of pumped storage stations in an existing electrical system has been previously observed worldwide. In Brazil, the combination of various favourable conditions stimulates the installation of pumped storage stations. In the analysis for the implementation of these stations it is fundamental the correct simulation of the electrical system operating conditions. The unstable behaviour of renewable and non dispatchable sources, the behaviour of pumped storage stations, and their contribution to optimization of power system operating conditions must be well modelled and investigated. Computational simulations are a cheap and accurate tool. The current work presents two real cases of operation simulations of pumped storage stations. One presents grid stability investigations and the other concerns computational simulations of back-to-back operation of a power plant. The first study gives an overview of investigations conducted for a variable speed project Frades II showing what impact requirements have on the unit and converter design. The back-to-back start procedure is performed according to the constraints imposed by the rated current on the starting circuit. Current and power during system acceleration are kept under acceptable levels.

Downloads

Não há dados estatísticos.

Referências

Canay, I. M., 1977. Extended synchronous machine model for calculation of transient

processes and stability, Electric machines and Electromechanics, vol. 1, pp. 137-150.

Nicolet, C., 2007. Hydroacoustic modelling and numerical simulation of unsteady operation

of hydroelectric systems, Thesis EPFL n° 3751, (http://library.epfl.ch/theses/?nr=3751).

Nicolet, C., Vaillant, Y., Kawkabani, B., Allenbach, P., Simond, J.-J., Avellan, F., 2008.

Pumped Storage Units to Stabilize Mixed Islanded Power Network: a Transient Analysis.

Proceedings of Hydro Vision 2008, Ljubljana, Slovenia, Paper 16.1.

Koutnik, J., Foust, J., Nicolet, C., Saiju, R., Kawkabani, B., 2010. Pump-Storage Integration

with Renewables ”“ Meeting the Needs Using Various Concepts, Proceedings of HydroVision

International, Charlotte, NC, USA, Session: Pumped-Storage Market Trends and Strategies,

paper 5, pp. 1-12.

Hodder, A., 2004. Double-fed asynchronous motor-generator equipped with a 3-level VSI

cascade, PhD Thesis No. 2939, École Polytechnique Fédérale de Lausanne.

Berndt, H., Hermann, M., 2007. Transmission Code 2007: Network and System Rules of the

German Transmission System Operator, Berlin.

National Grid Electricity Transmission, 2010. The Grid Code, Warwick.

Koutnik, J. et.al., 2008. Pump-Storage with adjustable speed ”“ Simulative comparison of

different variants, Proceedings of Hydro Vision International.

Simond, J.-J., Allenbach, P., Nicolet, C. and Avellan, F., 2006. Simulation tool linking

hydroelectric production sites and electrical networks, Proceedings of the 27th Int. Conf. on

Electrical Machines, ICEM, Chania, Greece.

Downloads

Publicado

2017-01-10

Como Citar

Koutnik, J., Zoby, M. R. G., Gonçalves, M. N. F., & Lopes, R. A. (2017). THE INTEGRATION OF PUMPED STORAGE STATIONS IN THE BRAZILIAN NATIONAL INTEGRATED SYSTEM: ELECTRICAL SYSTEM BEHAVIOUR ANALYSIS. Revista Interdisciplinar De Pesquisa Em Engenharia, 2(4), 110–122. https://doi.org/10.26512/ripe.v2i4.21460